Evaporation Losses Control — Cogico Terminal

Targeted vapor-loss control programme for gasoline storage tanks — monthly losses cut from 0.8 % to 0.05 % during peak summer through inspection-led calibration and modification of tank bodies and accessories.

Case study published 20 May 2026

Location
Jieh, Lebanon
Duration
5 months
End Client
Cogico
Role

Inspection · Root-Cause Analysis · Calibration & Modifications

Case study PDFÉtude de cas (FR)

0.8% → 0.05%
Monthly losses
-94%
Reduction
5 mo
Programme duration
Peak
Summer validated
Project Background

The context that shaped the engineering.

Evaporation losses are one of the costliest invisible problems in a gasoline storage terminal: product disappears, revenue with it, and emissions rise in parallel. Cogico's terminal at Jieh was experiencing losses of approximately 0.8 % per month — a level the operator had effectively accepted as the cost of doing business, especially through the summer heat. The objective of the engagement was to diagnose the actual root causes of those losses, rather than treat the symptom, and to deliver targeted corrective actions that would hold up under the worst-case operating condition: peak summer ambient temperatures.
Scope of Services

What was delivered.

01

Tank Inspection

Detailed inspection of tank bodies and accessories — seals, roof seams, breathing devices, vents and ancillary fittings.

02

Root-Cause Analysis

Identified the specific contributors driving vapor losses, distinguishing tank-fabric leaks from breathing-loss mechanisms.

03

Calibration & Modifications

Executed the necessary calibration and physical modifications to tank fittings and breathing equipment to address each identified loss path.

04

Performance Validation

Confirmed loss reduction under peak summer ambient conditions — the worst-case operating regime.

Design Solution

How the engineering came together.

Integrated multidisciplinary delivery

The programme refused to treat the 0.8 % loss as a single problem. Each loss path was diagnosed separately — seal condition, breathing valve setpoints, fitting integrity — and addressed with the appropriate intervention. The validation was deliberately scheduled for the hottest months of the year so that the corrective measures had to perform under the toughest thermal conditions before being signed off. The 94 % improvement was therefore a peak-summer figure, not a benign-season average.

Key Outcomes

The results the client took to operations.

94 % Loss Reduction

Monthly gasoline losses cut from 0.8 % to 0.05 % — sustained under peak summer ambient conditions.

Direct Cost Recovery

Product loss prevention translated directly into recovered revenue and reduced make-up purchases.

Environmental Compliance

Lower hydrocarbon emissions from the tank farm — improved environmental performance alongside the commercial gain.

Disciplines Covered

Multidisciplinary by design.

ProcessMechanicalStorage Tank EngineeringInspectionVapor-Loss ControlEnvironmental Compliance